GENERAL INFORMATIONS

GENERAL SPECIFICATIONS
Case: PC-ABS black color; self-extinguishing degree: V-0
according to UL 746C.
Front protection - designed and tested for IP 65 (*) and
NEMA 4X (*) for indoor locations (when panel gasket is
installed).
(*) Test were performed in accordance with CEI 70-1 and
NEMA 250-1991 STD.
Rear terminal block: screw terminals (screw M3, for
cables from φ 0.25 to φ 2.5 mm
2
or from AWG 22 to AWG
14 ) with connection diagrams and safety rear cover.
Weight:
360 g (0.8 lb) for TKS
450 g (1 lb) for MKS.
Power supply:
- 100V to 240V AC 50/60Hz (-15% to + 10% of the
nominal value).
- 24 V AC/DC (+ 10 % of the nominal value).
Power consumption: 5.5 W max.
Insulation resistance: > 100 MΩ according to
IEC 1010-1.
Dielectric strength: 2300 V rms according to
EN 61010-1.
Display updating time: 500 ms.
Sampling time:
250 ms for linear inputs
500 ms for TC and RTD inputs.
Control output updating time:
250 ms for linear inputs
500 ms for TC and RTD inputs.
Control output resolution: 0.1% of the span.
Instrument resolution: 30000 counts.
Accuracy: + 0,2% f.s.v.. + 1 digit @ 25 °C ambient
temperature.
Common mode rejection: 120 dB at 50/60 Hz.
Normal mode rejection: 60 dB at 50/60 Hz.
Electromagnetic compatibility and safety require-
ments: This instrument is marked CE.
Therefore, it is conforming to council directives 89/336/
EEC (reference harmonized standard EN 50081-2 and
EN 50082-2) and to council directives 73/23/EEC and
93/68/EEC (reference harmonized standard EN 61010-1).
Installation category: II
Pollution degree: 2
XKS-mA-1-A0.p65
25
Temperature drift: (CJ excluded)
< 200 ppm/°C of span for mV and TC ranges 1, 3, 5, 7, 20, 21,
22, 24.
< 300 ppm/°C of span for mA/V
< 400 ppm/°C of span for RTD range 11, 28 and TC ranges 0,
2, 4, 6, 23.
< 500 ppm/°C of span for RTD range 10 and TC ranges 8, 9,
25, 26.
< 800 ppm/°C of span for RTD range 27.
Operative temperature: from 0 to 50 °C.
Storage temperature : -20 to +70 °C
Humidity: from 20 % to 85% RH, non condensing.
Protections:
1) WATCH DOG circuit for automatic restart.
2) DIP SWITCH for protection against tampering of
configuration and calibration parameters.

MAINTENANCE

1) REMOVE POWER FROM THE POWER SUPPLY
TERMINALS AND FROM RELAY OUTPUT TERMI-
NALS
2) Remove the instrument from case.
3) Using a vacuum cleaner or a compressed air jet (max. 3
kg/cm
2
) remove all deposit of dust and dirt which may
be present on the louvers and on the internal circuits
trying to be careful for not damage the electronic
components.
4) To clean external plastic or rubber parts use only a cloth
moistened with:
- Ethyl Alcohol (pure or denatured) [C
- Isopropil Alcohol (pure or denatured) [(CH
- Water (H
O)
2
5) Verify that there are no loose terminals.
6) Before re-inserting the instrument in its case, be sure
that it is perfectly dry.
7) re-insert the instrument and turn it ON.