dir
= Out 2 is used as control output with direct
action (cooling).
AL1.P = it is used as Alarm 1 output and the alarm 1 is
programmed as process alarm.
AL1.b = it is used as Alarm 1 output and the alarm 1 is
programmed as band alarm.
AL1.d =it is used as Alarm 1 output and the alarm 1 is
programmed as deviation alarm.
NOTES
NOTES
NOTES
NOTES
NOTES:
Setting P9 = rEv, the "out 2cycle time" (Cy2) will be forced
to:
15 seconds when P10 = rEL
4 seconds when P10 = SSr
Setting P9 = dir, the "out 2cycle time" (Cy2) will be forced
to:
10 seconds when P25 = AIr
4 seconds when P25 = OIL
2 seconds when P25 = H2O
P10 = Output 2 type
P10 = Output 2 type
P10 = Output 2 type
P10 = Output 2 type
P10 = Output 2 type
This parameter is skipped when P9=nonE.
rEL = Relay
SSr = SSR
NOTES
NOTES
NOTES
NOTES:
NOTES
When P9=rEv and P10 = rEL, the "out 2cycle time" (Cy2)
will be forced to 15 seconds
When P9=rEv and P10 = SSr, the "out 2cycle time" (Cy2)
will be forced to 4 seconds
P11 = Alarm 1 operating mode
P11 = Alarm 1 operating mode
P11 = Alarm 1 operating mode
P11 = Alarm 1 operating mode
P11 = Alarm 1 operating mode
Available only when P9 = AL1.P, AL1,b or AL1.d.
H.A. = High alarm (outside for band alarm) with
automatic reset.
L.A. = Low alarm (inside for band alarm) with automatic
reset.
H.L. = High alarm (outside for band alarm) with manual
reset (latched).
L.L. = Low alarm (inside for band alarm) with manual
reset(latched).
P12 = Output 3 function
P12 = Output 3 function
P12 = Output 3 function
P12 = Output 3 function
P12 = Output 3 function
nonE
= output not used.
rEv
= Out 3 is used as control output with reverse
action (heating).
dir
= Out 3 is used as control output with direct
action (cooling).
XKS-mA-1-A0.p65
12
AL2.P = it is used as Alarm 2 output and the alarm 2 is
programmed as process alarm.
AL2.b = it is used as Alarm 2 output and the alarm 2 is
programmed as band alarm.
AL2.d =it is used as Alarm 2 output and the alarm 2 is
programmed as deviation alarm.
NOTE:
NOTE
NOTE
NOTE
NOTE
Setting P12 = rEv, the "out 3 cycle time" (Cy3) will be
forced to 15 seconds
Setting P12 = dir, the "out 3 cycle time" (Cy3) will be
forced to:
10 seconds when P25 = AIr
4 seconds when P25 = OIL
2 seconds when P25 = H2O
NOTES to P5, P9 and P12 relation.
NOTES to P5, P9 and P12 relation.
NOTES to P5, P9 and P12 relation.
NOTES to P5, P9 and P12 relation.
NOTES to P5, P9 and P12 relation.
1) Only 1 of the 3 outputs can be configured as "rEv".
2) Only 1 of the 3 outputs can be configured as "dir".
3) When none of the 3 outputs is configured as control
output the instrument will operate as a standard
indicator.
P13 = Alarm 2 operating mode
P13 = Alarm 2 operating mode
P13 = Alarm 2 operating mode
P13 = Alarm 2 operating mode
P13 = Alarm 2 operating mode
Available only when P12 = AL2.P, AL2.b or AL2.d.
H.A. = High alarm (outside for band alarm) with
automatic reset.
L.A. =
Low alarm (inside for band alarm) with automatic
reset.
H.L. = High alarm (outside for band alarm) with manual
reset(latched).
L.L. =
Low alarm (inside for band alarm) with manual
reset(latched).
P14 = Output 4 function
P14 = Output 4 function
P14 = Output 4 function
P14 = Output 4 function
P14 = Output 4 function
nonE
= output not used.
AL3.P = it is used as Alarm 3 output and the alarm 3 is
programmed as process alarm.
AL3.b = it is used as Alarm 3 output and the alarm 3 is
programmed as band alarm.
AL3.d =it is used as Alarm 3 output and the alarm 3 is
programmed as deviation alarm.
NOTE: The alarm 3 and the "Loop break alarm" are in OR
condition on the same output (OUT 4).