ero electronic MKS - mA Manuel De Service page 17

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

24 = TC type
N
range
-150 /
25 = TC type
R
range
0 /
26 = TC type
S
range
0 /
27 = RTD type
Pt 100 range
-199.9 /
28 = RTD type
Pt 100 range
-330 /
NOTE
NOTE
NOTE: selecting P1 = 0, 2, 4, 6, 10 or 27, the instrument
NOTE
NOTE
set automatically P44 = P45 = FLtr. For all the remaining
ranges it will set P44 = P45 = nOFL.
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
This parameter is available only when a linear input is
selected (P1 = 12, 13, 14, 15, 16, 17, 18 or 19).
----.
= No decimal figure.
---.-
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
1) When this parameter is modified, rL parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be greater than P4 in order to get a reverse
readout.
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.
Notes:
1) When this parameter is modified, rH parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be smaller than P3 in order to get a reverse
readout.
The initial and full scale values determine the input span
which is used by the PID algorithm, the SMART and the
alarm functions.
XKS-mA-1-A0.p65
11
+2550 °F
NOTE: the minimum input span (S = P4 - P3), in absolute
NOTE
NOTE
NOTE
NOTE
+3200 °F
value, should be set as follows:
+3200 °F
- For linear inputs, S > 100 units.
+400.0 °F
- For TC input with °C readout, S > 300 °C.
+1470 °F
- For TC input with °F readout, S > 550 °F.
- For RTD input with °C readout, S > 100 °C.
- For RTD input with °F readout, S > 200 °F.
P5 = Output 1 function
P5 = Output 1 function
P5 = Output 1 function
P5 = Output 1 function
P5 = Output 1 function
rEv
= Out 1 used as control output with reverse action
(heating).
dIr
= Out 1 used as control output with direct action
(cooling).
Pv.rt
= Out 1 retransmits the process variable.
SP.rt
= Out 1 retransmits the operative set point.
REVERSE ACTION
Input
t
Output
Output
t
P6 = Output 1 type
P6 = Output 1 type
P6 = Output 1 type
P6 = Output 1 type
P6 = Output 1 type
0-20 = output 1 type 0 - 20 mA
4-20 = output 1 type 4 - 20 mA
P7 = Retransmission - Initial scale value
P7 = Retransmission - Initial scale value
P7 = Retransmission - Initial scale value
P7 = Retransmission - Initial scale value
P7 = Retransmission - Initial scale value
P7 is available only when P5 = Pv.rt or SP.rt.
Range: from -1999 to 4000.
P8 = Retransmission - Full scale value
P8 = Retransmission - Full scale value
P8 = Retransmission - Full scale value
P8 = Retransmission - Full scale value
P8 = Retransmission - Full scale value
P8 is available only when P5 = Pv.rt or SP.rt.
Range: from -1999 to 4000.
P9 = Output 2 function.
P9 = Output 2 function.
P9 = Output 2 function.
P9 = Output 2 function.
P9 = Output 2 function.
nonE
= output not used.
rEv
= Out 2 is used as control output with reverse
action (heating).
GB
11
26/04/01, 16.46
DIRECT ACTION
Input
t
t