The sensor leads break can be signalled as:
- for TC/mV input
:
OVERRANGE or UNDERRANGE
selected by a solder jumper
- for RTD input
:
OVERRANGE
- for mA/V input
:
UNDERRANGE
Note: On the mA/V input the leads break can be detected
only when the range selected has a zero elevation (4/20
mA or 1/5 V or 2/10 V)
On RTD input a special test is provided to signal
OVERRANGE when input resistance is less than 15 ohm
(Short circuit sensor detection).
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
The instrument performs same self-diagnostic algorithm.
When an error is detected, the instrument shows on the
lower display the "Err" indication while the upper display
shows the code of the detected error.
ERROR LIST
ERROR LIST
ERROR LIST
ERROR LIST
ERROR LIST
SEr
Serial interface parameter error
100
Write EEPROM error.
150
CPU error.
200
Tentative to write on protected memory.
201 - 2xx
Configuration parameter error. The two
less significant digits shown the number of
the wrong parameter (ex. 209 Err shows
an Error on P9 parameter)
299
Error in control outputs selection
301
Error on calibration of the selected input
307
RJ input calibration error
320
Linear output calibration error
400
Control parameters error
500
Auto-zero error
502
RJ error
510
Error during calibration procedure
NOTE
NOTE
NOTE
NOTE
NOTE
1) When a configuration parameter error is detected, it is
sufficient to repeat the configuration procedure of the
specify parameter.
2) If an error 400 is detected, push the t push-button
XKS-mA-1-A0.p65
24
and, maintaining the pressure, push the s push-button
and load the default parameters; at this point repeat
control parameter setting.
3) For all the other errors, contact your supplier.