VOLTAGE OUTPUTS FOR SSR DRIVE
+
16
+
OUT 2
_
_
17
SOLID STATE
RELAY
Fig. 9 SSR DRIVE OUTPUT WIRING
It is a time proportioning output.
Logic level 0: Vout < 0.5 V DC.
Logic level 1: Maximum current = 20 mA.
- 14 V ± 20% @ 20 mA
- 24 V ± 20% @ 1 mA.
NOTE: This output is not isolated. A duble or reinforced
isolation between instrument output and power supply must
be assured by the external solid state relay.
XKS-mA-1-A0.p65
5
LINEAR OUTPUT
This instrument is equipped with one isolated linear output
(OUT 1) programmable as:
- main output (heating or cooling)
- secondary output (cooling)
- analog retransmission of the measured value
- analog retransmission of the operative set point.
+
14
OUT 1
_
15
Fig. 10 mA OUTPUT WIRING
Output type: isolated 0 - 20 or 4 - 20 mA programmable.
Maximum load: 500 Ω.
Resolution:
- 0.1% when used as control output
- 0.05 % when used as analog retransmission.
GB
5
26/04/01, 16.46
+
_