Assembly Of The Attachment Pieces - Kessel InnoCleanPLUS EL 80 Instructions De Montage

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 47
4.8 Laying the connecting lines to the control unit
(ventilation hose and control line)
The control line and the ventilation hose must be laid in the
cable conduit between valve block and control unit (seePro-
cedure)
Procedure:
- Open the locking bracket on the valve block inside the tank
- Remove the valve block from the adapter plate
- Pull the grey ventilation hose and control line through the
cable conduit
- Connect the ventilation hose on the valve block using a
quick-action coupling (see 4.11 Point 5)
- Insert valve block on adapter plate
Adapter plate
Recess for
attaching the
control line
Control line
Air hoses to the compressed air syphons

4.9 Assembly of the attachment pieces

4. Installation and assembly
Air hose to the compressor
Quick-action coupling
Valve block
Locking bracket
Min. 100 mm
Min. 100 mm
109
- caution: The control line must be placed in the recess (see
figure) in order to ensure a correct latch with the adapter
plate.
- Check valve block for correct seat and close the locking
lever
Air connection manifold
Air hose with compressor
Wastewater loading
system
Sludge transfer system
First, place the gasket (see drawing 4.9) provided into the
opening in the dome.
Grease the bottom part of the telescopic KESSEL attachment
piece with lubricant and place into the tank opening, bring into
the desired position and fasten by means of a clamping ring
(optional accessory). Alternatively, it is also possible to apply
lubricant to the sealing ring. With the aid of the existing clam-
ping ring it is now possible to fasten the attachment piece in
the desired position (alignment with the top ground surface).
The fine adjustment to the final height is then effected with the
adjusting screws. A ground slope can be compensated for
with the continuously height-adjustable and up to 5° inclina-
ble attachment piece. The disposal stickers included in the
supply must be attached to the cleaned and dry surface on
the attachment piece (see illustration).
Important: The green disposal sticker must be placed on the
inlet side and the red one on the drain side!
The attachment piece must afterwards be sufficiently backfil-
led and compacted.
Aeration tube
clear water removal system

Publicité

Table des Matières
loading

Table des Matières