Installing The Device; Fluid And Pneumatic Connection - Burkert 8835 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.2

Installing the device

The device can be installed in any position, preferably with
the actuators of the heating circuit valves face up.
Observe flow direction!
We recommend using Multi-Silikonfett OKS 1110 (silicone grease)
for sealing hose connections and O-rings.
Information can be found in Chapter
"9.6 Recommended auxiliary materials".
Attach the device via the mounting holes
(see "6.5.1 Mechanical data").
7.3

Fluid and pneumatic connection

NOTE!
Damage to the device.
Blocked or soiled pipelines may impair the function of the device
or cause a failure.
▶ Before connecting the device, clean the pipelines thoroughly.
12
english
Type 8835
Assemblyandinstallation
7.3.1 Fluid connection
DANGER!
Injury caused by high medium pressure.
Burns caused by hot lines and discharge of hot medium.
▶ Before loosening lines or valves, leave the device to cool down,
turn off the pressure and drain the lines.
Twisted line connections can lead to leaks.
▶ Make sure that the pipes are in alignment and the line connec-
tors are not twisted during the assembly.
1
2
3
5
4

Publicité

Table des Matières
loading

Table des Matières