9.1.4 Performing voltage tests

When voltage tests are carried out on electrical installa­
tions equipped with AC/DC sensitive residual current devic­
es (FI/RCDs) of type B/B+, these could sustain damage due
to incorrectly performed tests.
T
ATTENTION
Material damage of protective element due to incor-
rectly performed test
Incorrectly performed tests can damage protective
elements.
f In the case of voltage tests with test voltages > 0.5 kV,
switch off the residual current devices (FI/RCDs) and
the upstream and/or downstream circuit breakers.
Fig.: 24. Voltage test
f During voltage testing, also pay attention to the circuit
diagram shown.
54

9.1.5 Removing the floor panel

The floor panel of the device can be opened for mainte­
nance and repair purposes.
When doing so, the device must not be connected to the
power supply.
f Take the device out of service.
¨
Section 8
Fig.: 25. Removing the floor panel
f Place the device on the top side.
f Remove the circumferential screws (1) of the floor panel
(2) with a suitable tool.
f Remove the floor panel.
2
1