Electrical Connection; Voltage Supply / Supply Network Connection - Mennekes Basic 3,7 Instructions De Fonctionnement Et D'installation

Masquer les pouces Voir aussi pour Basic 3,7:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5.3 Electrical connection

5.3.1 Voltage supply / supply network connection

T
T
DANGER
Danger to life due to incorrect connection.
RCCBs (type B) sensitive to universal currents may not
installed behind RCCBs (type A) sensitive to pulse currents.
Note the following points when connecting to the power
supply:
f Observe DIN VDE 0100, part 530.
f Make sure that the charging system is not installed
behind RCCBs (type B) sensitive to pulse currents.
f Please comply also with local requirements.
Note the following points when connecting to the power
supply:
„ This device may be installed, commissioned and
serviced only by a qualified electrician in accordance
with relevant national regulations; see Chapter "2.1
Target groups".
„ Before connecting the device, caution must be taken
to ensure that it is free of voltage or the appropriate
protective measures have been taken.
14
The charging column may be connected only to a TN-S
system.
Fig.: 16. Terminal block in charging column
Connect the supply line:
f Connect the supply line according to the terminal
labelling (for tightening torque, see the Chapter "4.
Technical Data").
f Check that the individual cores are connected correctly
and that the screws are tightened.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Basic 11Basic 22Basic s 22

Table des Matières