UPS Models
BATTERY CHARGER STAGE
Nominal voltage
Maximum recharge current
Battery charger algorithm
Technology
Input voltage tolerance for recharging at maximum
current
DIMENSIONS AND WEIGHT
W x D x H
Weight
OTHER FEATURES
Noise
Colour
(7)
Ambient temperature
(1)
@ 100% load & THDv ≤ 1%
(2)
In order to keep the output voltage within the indicated precision range, a recalibration may be necessary, following a long period of use.
(3)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronised with the mains. If the frequency is out of the tolerance
range, or in battery operation, the frequency will be the selected +0.01%
(4)
Mains/Battery @ 0% -100% load
(5)
@ Mains / battery / mains @ 0% / 100% / 0% resistive load
(6)
The recharge current is adjusted automatically, depending on the capacity of the battery installed.
(7)
20 – 25 °C for a longer battery life
R
L
EDUCING THE
OAD
If the output voltage is set to 115V and 110V (see "Configuring the UPS" paragraph), the maximum power output of the UPS is
reduced with respect to its rated value.
228 (Ph-Ph) ; 132 (Ph-N) = NO power output downgrading
220 (Ph-Ph) ; 127 (Ph-N) = NO power output downgrading
208 (Ph-Ph) ; 120 (Ph-N) = NO power output downgrading
199 (Ph-Ph) ; 115 (Ph-N) = 5% power output downgrading
190 (Ph-Ph) ; 110 (Ph-N) = 10% power output downgrading
(6)
(
115V
110V)
TO
AND
30kVA
240Vdc
10A
Two levels with temperature compensation
Analogue switching current under P control
(PWM voltage and charge current adjustment)
190-264Vac
440 x 850 x 1320 mm
280 Kg
≤ 48dB(A)
RAL 7016 + RAL 7012 (door central area)
0 – 40 °C
74
40 kVA
290 Kg