Power Reduction For 200/208V Phase - Neutral Loads; Configuring The Ups - Gtec SATURN Série Manuel D'installation

Masquer les pouces Voir aussi pour SATURN Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

P
OWER REDUCTION FOR
In case the output voltage is set to 200V or 208V PHASE-NEUTRAL (see the "Configuring the UPS" paragraph), the maximum
power output of the UPS is reduced compared to its nominal value, as shown in the diagram below:
C
ONFIGURING THE
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
Language*
Output voltage
Buzzer
Operating mode**
Battery low **
Date and time**
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
200/208V
UPS
DESCRIPTION
Selects mimic panel
language language
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
Selects one of five different
operating modes
Estimated autonomy time
remaining for "battery low"
warning
UPS internal watch setup
-
PHASE
NEUTRAL LOADS
DEFAULT
POSSIBLE CONFIGURATIONS
 English
 Italian
English
 German
 French
 220V
 230V
230V
 240V
 Normal
 Reduced: does not sound due to the
Reduced
momentary intervention of the bypass
 ON LINE
 ECO
ON LINE
 SMART ACTIVE
 STAND-BY OFF
 1 ÷ 7 @1 min step
3 min.
101
 Spanish
 Polish
 Russian
 Chinese

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Saturn 30Saturn 40

Table des Matières