Type 5: Data error in control circuit alarm
To solve this type of error you need to make a total reset with the advanced setup feature.
If this does not solve the error, the circuit has to sent back for a factory reprogramming.
See 5 in table below
Type 6: Fire alarm contact (connected to external fire alarm system)
See 6 in table below
Type 7: maintenance alarm. It can be configured in 2 steps (via the advanced setup):
SERVICE ALARM: this alarm indicates that the fan operation time reached the limit set in the configuration.
This alarm does not generate a fan stop.
VEN.STOP SERVICE: alarm indicates that the fan operation time reached the limit set in the configuration.
This alarm generates a fan stop.
See 7 in table below.
Type 8: Communication alarm between CBr4 and CPT.
See 8 in table below.
Displayed text
Type
(1)
1
ALARM
VENTx
2
PRESSURE
ALARM
3
Pa INIT
ALARM
4
CA, LS of CP
ALARM
5
DATA
ERROR
6
FIRE
ALARM
7
ALARM
SERVICE
FAN.STOP
SERVICE
8
COM
ERROR
/ = no action taken for this type of alarm
(1) Explicit text explaining the alarm is displayed on LCD in several successive screens
For complete details see our technical documentation on our site www.swegon.com.
(2) Fans can be stopped if configured via the advanced setup. You can configure to stop F1/F2 or F3/F4 or F1/F2/F3/F4.
If only 2 fans are stopped on the 4 then the 2 others will go to the set airflow value configured via the advanced setup.
(3) When one set of fan is stopped (F1/2 or F3/4), the other set can be programmed to deliver a specific airflow
Wiring diagram: see schematic
9) Controlling external relays
Control of the external relays is made by means of 5 knobs UP / DOWN / LIGHT / UV / GAS on CPT.
Wiring diagram ; see drawing
Actions on the CPT
LED
LED Pa
Buzzer
ALARM
Red
/
/
Red
Red
/
Red
/
Red
/
Red
/
Red
/
Red
/
Red
/
.
.
2 in appendix 1
.
.3 in appendix 1
Actions on the CBr4
LED
R1 Relay
ALARM
ON
ON
Alarm status
ON
ON
ON
ON
Alarm status
ON
ON
Alarm status
ON
ON
Alarm status
ON
ON
Alarm status
ON
ON
Alarm status
ON
ON
ON
Blink
Alarm status
Action on
SAT3 R2
relay
/
/
Dicht
/
/
/
/
/
/
/
fans
/
/
(2)
Stop
/
Stop
Stop
(3)
/
Stop
Stop
24