5) Configuration
The configuration is made using the LCD screen and 4 buttons SETUP, ↑, ↓ and ENTER of the
CPT.
To start the configuration:
- Press on the selection knob of the CPT (left on photo) so that the SETUP LED ignites.
- Press 'SETUP' until the text 'SETUP' appears on the screen.
Principle: select via buttons ↑ ↓, then press ENTER to validate. The numbers are introduced
figure by figure.
1
LANGUAGE
2
DISPLAY m³h?
3
DISPLAY Pa?
4
DISPLAY m/s?
SURFACE?
5
x,xxxxm²
6
FAN TYPE
7
# FAN
8
POSITION
9
MODE
IF OFF MODE
10
END SETUP
IF CA MODE
10
m³h K1?
11
m³h K2?
12
m³h K3?
9
%F34/F12
PRESSURE
10
ALARM?
∆P FAN1
11
∆P FAN3
12
13
INIT Pa REF?
14
m³h INIT
Pa REF INIT
15
xxxx m³h
xxxx Pa
16
END SETUP
Language choice
Display airflow in info display loop ?
Display static pressure in info display loop ?
Display air speed in info display loop ?
If you selected YES in 4, enter surface in m² to convert airflow in airspeed.
Choice of fan through (CID – see label on fan) All fans must be of the same type.
Select number of fans connected to CB (1,2,3 or 4).
Select entry for connection of the fan(s) on the CB :
If only 1 fan it must be F1
If 2 fans either F1 F3 or F1 F2
If 3 fans: F1 F2 F3 or F1 F3 F4
If 4 fans: the CB automatically selects F1 F2 F3 F4.
Choice of working mode (OFF, CA, LS, CPf, CPs)
The configuration of the system is finished.
This working mode allows to stop the fans with the CPT while CBr4 is master.
Enter airflow 1 (with airflow F1=airflow F2). Airflow is activated when contact between K1
and +12V is closed, or if position I is set on CPT.
Enter airflow 2 (with airflow F1=airflow F2). Airflow is activated when contact between K2
and +12V is closed, or if position II is set on CPT.
Enter airflow 3 (with airflow F1=airflow F2). Airflow is activated when contact between K3
and +12V is closed, or if position III is set on CPT.
Select airflow ratio between fans F3,F4 and fans F1,F2
Pressure alarm is optional. Of you do not wish to set a pressure alarm select N(o),
otherwise select Y(es)
If you have selected Y: Configuration of pressure alarm on fan F1:
Select value of pressure increment corresponding to the nominal airflow.
Configuration of pressure alarm on fan F3
Configuration of pressure alarm: Do you wish to (re)define the nominal pressure (different
for F1 and F3 fans) corresponding to a new nominal airflow ?
If you have selected Y: Pressure alarm setup :Enter airflow to define reference pressure.
Initialisation of the reference pressure busy. After 1 minute the CB will memorize the value
of the calculated static pressure on the fan once the INIT airflow is reached.
Display of actual pressure and airflow
The setup is then completed.