Code
Level Descr.
List of -diS display parameters
ndt
1
Decimal point display
0 = display without decimal point
1 = display with decimal point.
ddL
1
Display during the defrosting phase
0 = normal display (as set from the ddd par.)
1 = freezes the temperature value displayed at the start of defrosting
until the end of defrosting and the reaching of the setpoint
2 = "dF" until the end of defrosting and the reaching of the setpoint
The ddL parameter can be controlled only if the standard display (ddd
par.) includes the adjustment probe (probe 1 or network probe)
Ldd
1
Defrosting display block timeout
The time, starting from the end of defrosting (end of dripping
phase),after which the normal display is in any case restored
dro
1
°C or °F selection
0 = °C
1 = °F
This selection only affects temperature measurements. The values of
the parameters concerning temperature maintain their current values
and therefore, they must be varied manually to adapt them to the
Fahrenheit scale.
List of -CnF configuration parameters
LOC
1
Keyboard lock
(**)
0 = keyboards disabled
1 = main terminal keyboard enabled
2 = secondary terminal keyboard enabled
3 = keyboards enabled (the first to request a service has precedence
until completion)
rEL
1
Software release
A read-only value that identifies the software version
List of -Lan(***) network parameters
dEA
1
Supervision network address (for Master only)
The address to be set on each master must take into account the
number of slaves present in the LAN network preceding it:
"dEA"="dEA[previous master]"+"L01[previous master]"+1
The Supervision network address for a Slave is "dEA[master]"+"L00")
For models PTM068Z012, PTM080Z012, PTL060Z012, PTL080Z012, PTM110Z012, PTM140Z012, PTM200Z012, PTL130Z012,
PTL180Z012, PTL200Z012, PTL260Z012, PTM300Z012, PTM370Z012, PTL350Z012 and PTL450Z012 the parameters dtY, dEt
and dSt have the values (tolerance defrosting) reported in Table 7.
Livello
dtY
1
Defrosting type
0 = heating element: ends at temperature or
after maximum safe time (timeout)
1 = hot gas: ends at temperature or after
maximum safe time (timeout)
For defrosting using a heating element, there is
a 1 second delay between the compressor
switching off and the defrosting relay being
triggered
dEt
1
Defrosting timeout (Defrosting by heater)
When the set time expires, defrosting is in any
case ended, even if the defrost end temperature
has not been reached, passing on to the drip
phase
dSt
1
Defrost end temperature (Defrosting by heater)
The probe 2 temperature above which
defrosting is ended. If, at the start of a
defrosting cycle, the temperature is greater than
that set, no defrosting will be carried out. In the
event of a probe 2 malfunction, the defrosting
cycle will in any case terminate after reaching a
time limit
table 7
Descrizione
Range
0,1
0,1,2
0 ... 255
0,1
0 ... 3
0.0 ... 99.9
1 ... 199
Range
Unità
0,1
1 ...
min
250
-50.0
...
°C
199.
[°F]
0
Unit
MBP
LBP
per SV)
flag
1
1
0
0
min
6
6
flag
0
0
1
1
-
-
1
1
MBP
LBP
HBP
0
0
0
30
30
30
15
15
10
P-SF-SV Pag. 54 Rev 00 02/11