ATTENTION:
4.3.2. P Series Plug-In Version Installation Method
To proceed to installation of the machine, use the following procedure:
1.
On the wall of the coldroom, based on the model, make a hole of suitable dimensions as indicated in the pages from Figure
8 to Figure 12 of Chapter 9 at the end of the handbook.
2.
Lift the machine with the hoist or another suitable vehicle in compliance with the lifting instructions in Figure 2.
3.
Position the machine in the hole made in the wall of the coldroom and place the evaporating part in from outside.
4.
Fasten the machine to the wall of the coldroom using the specific screws supplied.
5.
Seal the perimeter of the plug-in with silicon (suitable for use in the coldroom) to avoid infiltration of warm air inside the
coldroom. On the upper side, perform the operation before positioning.
ATTENTION:
ATTENTION:
Models PTM300 / PTM370 / PTL350 / PTL450 have two support legs supplied. For assembly positioning, see Figure 12.
4.3.3. P Series Saddle Version Installation Method
To proceed to installation of the machine, use the following procedure:
1.
Before assembly on the coldroom ceiling, make 2 grooves on the upper ends of the wall and a hole for water drainage, as
indicated in the pages in Figure 9 at chapter 9 at the end of handbook
2.
Lift the machine with the hoist or another suitable vehicle in compliance with the lifting instructions in Figure 2.
3.
Position the machine on the grooves made on the wall of the coldroom.
4.
Fasten the machine to the wall of the coldroom using the specific screws supplied.
5.
Seal the perimeter of the grooves with silicon (suitable for use in the coldroom) to avoid infiltration of warm air inside the
coldroom (Figure 6).
the machine is equipped with a condensate water evaporation tank. We recommend you connect a
rubber tube to the overflow tube to enable evacuation of water in case of functioning or use
anomalies.
if the machine has a condensate water evaporation tank, we recommend you connect a rubber tube
to the overflow tube to enable evacuation of water in case of functioning or use anomalies.
if the machine is not equipped with a condensate water evaporation tank, lengthen the drainage tube
outside the coldroom by using a siphon
Figure 5 – Machine positioning in coldroom.
P-SF-SV Pag. 48 Rev 00 02/11