Rivacold P Mode D'emploi Et D'entretien page 52

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

UK
Code
Level Descr.
diF
1
Differential
temperature > setpoint + diff. -> adjustment On
temperature ≤ setpoint -> adjustment Off
List of -Pro probe parameters
CA1
1
Probe 1 calibration
CA2
1
Probe 2 calibration
CA3
1
Probe 3 calibration
List of -CPr compressor parameters
Ont
1
Compressor ON time in the
event of probe failure
OFt
1
Compressor OFF time in the
event of probe failure
dOn
1
Compressor activation delay
The time, starting from the switch on request, after which the
compressor is effectively activated.
In the event of network control in sequential mode, this represents the
activation delay from compressor to compressor
dOF
1
Minimum compressor OFF time
The time, starting from the moment of deactivation, for which it is not
possible to restart the compressor
dbi
1
Delay between switch on times
The time, starting from the moment of previous activation, for which
the compressor cannot be restarted.
OdO
1
Outputs delay at power-on (compressor, fans, defrosting)
This is used to delay the enabling of adjustments after the instrument
has been switched on for a set amount of time.
The transition from stand-by to machine activated (ON command
from the keyboard) bypasses this delay
List of -dEF defrosting parameters
dtY*
1
Defrosting type
0 = heating element: ends at temperature or after maximum safe time
(timeout)
1 = hot gas: ends at temperature or after maximum safe time
(timeout)
For defrosting using a heating element, there is a 1 second delay
between the compressor switching off and the defrosting relay being
triggered
dit
1
Defrosting interval
The maximum time (from start to start) between two consecutive
defrosting cycles. When this time expires, a defrosting cycle is enabled
(cyclical defrosting). The timer is reset at each defrosting request (even
if not cyclical).
0 = cyclical defrosting disabled
dct
1
Defrosting interval count mode
0 = counts if the compressor is operating
1 = counts all the time
dOH
1
Defrosting start delay at power-on
The time, as from when the instrument is switched on, for which any
defrosting requests are frozen (manual defrosting excluded)
dEt*
1
Defrosting timeout
When the set time expires, defrosting is in any case ended, even if the
defrost end temperature has not been reached, passing on to the drip
phase
dSt*
1
Defrost end temperature
The probe 2 temperature above which defrosting is ended. If, at the
start of a defrosting cycle, the temperature is greater than that set, no
defrosting will be carried out. In the event of a probe 2 malfunction,
the defrosting cycle will in any case terminate after reaching a time
limit
The value assigned to this
parameter is added to (positive
value) or taken away from (negative
value) the temperature detected by
the probe
In the event of an adjustment probe
error, the compressor is enabled in
cyclical mode with set operation and
off times. In particular:
Ont=0: the compressor remains off
Ont>0 and OFt=0: the compressor
remains on
Range
Unit
MBP
0.1 ...
°C [°F]
2
50.0
°C [°F]
0
-20.0 ...
0
20.0
0
0 ... 60
min
15
0 ... 60
min
15
0 ... 250
sec
0
0 ... 60
min
3
0 ... 60
min
0
0 ... 60
min
3
0,1
1
0 ... 250
h
6
0,1
1
0 ... 250
min
0
1 ... 250
min
15
-50.0 ...
°C [°F]
10
199.0
P-SF-SV Pag. 52 Rev 00 02/11
LBP
HBP
(non
per SV)
2
2
0
0
0
0
0
0
15
15
15
15
0
0
3
3
0
0
3
3
1
0
6
6
1
1
0
0
15
15
15
10