Mechanical installation
Wall mounting
Wiring on the motor side
{
Danger!
All control terminals only have basic insulation (single isolating distance)
ƒ
after connecting a PTC thermistor or a thermal contact.
Protection against accidental contact in case of a defective isolating
ƒ
distance is only guaranteed through external measures, e. g. double
insulation.
}
Danger!
The connection between terminal X2 and sheet must not be released!
!
3.4 Nm
30 lb-in
5.5 mm
Use low−capacitance motor cable! (core/core £ 75 pF/m, core/shield £ 150 pF/m)
0
A motor cable that is as short as possible has a positive effect on the drive behaviour!
Cable cross−sections U, V, W, PE:
E82MV251_2B
E82MV371_2B
1
Install a separate cable (shielded) to X2/T1 and X2/T2 for the motor temperature monitoring.
Install control cables and mains cables with a spatial separation from the motor cable!
94
A
B
X2
1a
®
2
1 mm
(AWG 18), shielded
®
2
1 mm
(AWG 18), shielded
l
0.5...0.6 Nm
4.4...5.3 lb-in
2.5 mm
AWG 12
W V
U
PE T2 T1
T2
5.5 mm
PE
EDK82MV371 DE/EN/FR 7.0
2
6mm
X2
T1
J >
8200mot052