Commissioning
Linear V/f−characteristic control
Switch−on sequence
14.
If you want to change the settings, go to the ALL
menu
15.
Go to the menu ALL
A Check the fan monitoring setting under code
C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2
kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may
be destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
16.
Select setpoint
17.
Enable the controller
18.
The drive is now running.
112
Comment
For instance activate JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
E.g. via potentiometer at
terminals 7, 8, 9
Terminal X3/28 = HIGH
If the drive does not start, additionally
press u