7
Commissioning
Important controller codes
Code
No.
Name
C0012
Acceleration
time main
uSEr
setpoint
C0013
Deceleration
time main
uSEr
setpoint
C0014
Operating
v
mode
C0015
V/f rated
frequency
uSEr
124
Possible settings
Lenze
Selection
5.00
0.00
5.00
0.00
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
boost)
min
3
V/f characteristic control V ~ f
(square−law characteristic with
constant V
4
Vector control
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum
frequency (C0011)
50.00 7.50
{0.02 s}
{0.02 s}
2
boost)
min
{0.02
Hz}
l
IMPORTANT
1300.00 Reference: frequency
change 0 Hz ... C0011
l
Additional setpoint
ðC0220
l
Acceleration times
that can be activated
via digital signals ð
C0101
1300.00 Reference: frequency
change C0011... 0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times
that can be activated
via digital signals ð
C0103
l
Commissioning is
possible without
identifying motor
parameters
l
Advantage of
identification with
C0148:
– Improved smooth
running at low
speeds
– V/f rated
frequency (C0015)
and slip (C0021)
are calculated and
saved. They do not
have to be entered
In the case of the first
selection enter the
motor data and identify
them with C0148
Otherwise
commissioning is not
possible
When C0014 = 5, C0019
must be set = 0
(automatic DC injection
brake is deactivated)
960.00
l
C0015 is calculated
and saved during the
motor parameter
identification with
C0148.
l
The setting applies to
all permitted mains
voltages
EDK82MV371 DE/EN/FR 7.0