Table Des Matières; How To Test Ac Voltages; How To Test The Polarity At Dc Voltage; Technical Data - Benning PROFIPOL Mode D'emploi

Masquer les pouces Voir aussi pour PROFIPOL:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 3
Bedienungsanleitung
D
F
E
Инструкция за експлоатация
Návod k použití zkoušečky
Brugsanvisning
Käyttöohje
Οδηγίες χρήσεως
Használati utasítás
H
Istruzioni per l'uso
I
Benning Elektrotechnik & Elektronik GmbH & Co. KG
Münsterstraße 135 - 137 • D - 46397 Bocholt
Phone: +49 (0) 2871 - 93 - 0 • Fax: +49 (0) 2871 - 93 - 429
www.benning.de • E-Mail: duspol@benning.de
Naudojimosi instrukcija
Bruksanvisning
N
Gebruiksaanwijzing
Instrukcja obsługi
Instrucţiuni de utilizare
S
Bruksanvisning
Kullanma Talimati
Priručnik za upotrebu
3
4
5
A
B
6
geprüft und zugelassen
Operating manual
PROFIPOL
®
Before using the voltage tester PROFIPOL
read the operating manual carefully and always
observe the safety instructions!
List of contents:
1.
Safety instructions
2.
Functional description of the voltage tester
3.
Functional test of the voltage tester
4.
5.

How to test DC voltages

6.
7.

General maintenance

8.

Environmental notice

1.
Safety instructions:
-
�old the �oltage tester only by the insulated
handles
and
and do not touch the contact
electrodes (probe tips) !
-
I��ediately before use: Check the �oltage tester
for correct operation! (see chapter 3). The �oltage
tester �ust not be used if one or se�eral display
functions fail or if the �oltage tester is not ready to
operate (IEC 61243-3)!
-
-
The �oltage tester co�plies with protection class
IP 65 and therefore can also be used under wet
conditions.
-
For testing, fir�ly grasp the �oltage tester by the
handles
and
.
-
longer than 30 seconds (�axi�u� per�issible
operating ti�e = 30 s)!
-
The �oltage tester only operates correctly
within the te�perature range of -10 °C up to
+55 °C at relati�e air hu�idity of 20 % up to 96 %.
-
Do not dis�antle the �oltage tester!
-
Please protect the housing of the �oltage tester
against contamination and damages.
-
Please store the �oltage tester under dry conditions.
Attention:
After �axi�u� load (i.e. after a �easure�ent of 30
seconds at 400 V), the �oltage tester �ust not be used
for a duration of 300 seconds!
2.
Functional description
The PROFIPOL
is a two-pole �oltage tester according
®
to IEC 61243-3 with �isual display  and without own
power supply. The �oltage tester is designed for DC
and AC �oltage tests within the �oltage range of 6 V
up to 400 V. It can be used to perfor� polarity tests
in DC.
The �oltage tester consists of the test probes L1
and L2
and a connecting cable 6. The test probe
L1
is equipped with a display .
Display field
The display syste�  consists of high-contrast light-
e�itting diodes (LED) 3 indicating �oltages in steps
of 6 V to 400 V. The indicated �oltages are no�inal
�oltages. With DC �oltage, the LEDs also indicate the
polarity (see chapter 5).
3.
Functional check
-

The �oltage tester �ust be used only within the

no�inal �oltage range of 6 V up to 400 V!

-

Ne�er connect the �oltage tester to �oltage for

longer than 30 seconds (�axi�u� per�issible
operating ti�e = 30 s)!
-
Check the �oltage tester for correct function
i��ediately before use!
-
Test all functions by �eans of known �oltage
sources.
For DC �oltage tests use e.g. a car battery.
For AC �oltage tests use e.g. a 230 V socket.
Do not use the �oltage tester unless all functions are
operating correctly!

4. How to test AC voltages

-
The �oltage tester �ust be used only within the
no�inal �oltage range of 6 V up to 400 V!
-
Ne�er connect the �oltage tester to �oltage for
longer than 30 seconds (�axi�u� per�issible
operating ti�e = 30 s)!
-
Place the contact electrodes  of the test probes
L1
and L2

against the rele�ant points of the

unit under test.
-
For AC �oltages fro� 6 V onwards the LEDs "plus"
and "�inus" 4 and 5 light up. Further�ore,
all LEDs light until the step �alue of the applied
voltage is reached.
5.
-
The �oltage tester �ust be used only within the
no�inal �oltage range of 6 V up to 400 V!
-
Ne�er connect the �oltage tester to �oltage for
longer than 30 seconds (�axi�u� per�issible
operating ti�e = 30 s)!
®
: Please
-
Place the contact electrodes  of the test probes
L1
and L2
unit under test.
-
and "�inus" 4 and 5 light up. Further�ore,
all LEDs light until the step �alue of the applied
voltage is reached.

5.1 How to test the polarity at DC voltage

-
The �oltage tester �ust be used only within the
no�inal �oltage range of 6 V up to 400 V!
-
Ne�er connect the �oltage tester to �oltage for
longer than 30 seconds (�axi�u� per�issible
operating ti�e = 30 s)!
-
Place the contact electrodes  of the test probes
L1
and L2
against the rele�ant points of the
unit under test.
-
If LED 4 lights up, the "positi�e pole" of the unit
under test is at test probe
-
If LED 5 lights up, the "negati�e pole" of the unit
under test is at test probe
6.

Technical data

-
�uideline for two-pole �oltage testers: IEC 61243-3
-
Protection class: IP 65, IEC 60529 (DIN 40050)
IP 65 �eans: Protection against access to
dangerous parts and protection against solid
i�purities, dustproof, (6 - first index). Protected
against water jets, (0 - second index).
-
No�inal �oltage range: 6 V to 400 V
-
Internal resistance, �easuring circuit: 130 kΩ
-
Current consu�ption: �ax. I
-
Polarity indication: LED +; LED -
(indicating handle = positi�e polarity)
-
Indicating steps LED: 6 V, 12 V, 50 V, 120 V, 230 V,
400 V
-
�ax. indicating errors: �
± 15 %, ELV �
n
-
No�inal frequency range f: 0 to 500 �z
-
�ax. per�issible operating ti�e:
ED = 30 s (�ax. 30 seconds), 300 s pause
-
Weight: approx. 136 g
-
Connecting cable length: approx. 830 ��
-
Operating and storing te�perature range: -10 °C
up to +55 °C (cli�ate category N)
-
Relati�e air hu�idity: 20 % up to 96 % (cli�ate
category N)
7.
Clean the exterior of the housing with a clean dry
cloth (exception: special cleansing cloths). Do not use
solvents and/ or abrasives to clean the voltage tester.
8.
At the end of the product's useful life, please
dispose of it at appropriate collection points
pro�ided in your country.
.
.
3.1 �A