Indication D'anomalie - Surcharge (Ol) - YASKAWA GPD 506/P5 Manuel Technique

Table des Matières

Publicité

SCHÉMA DE DÉPANNAGE 6.6
INDICATION D'ANOMALIE —
CHARGE TROP ÉLEVÉE
(SURCHAUFFE DU MOTEUR)?
NON
SÉLECTION DE V/f
ADÉQUATE?
OUI
PLUS D'UN MOTEUR
SUR L'UNITÉ?
NON
LA PROTECTION CONTRE LA
SURCHARGE THERMIQUE (n033 )
EST-ELLE PROGRAMMÉE
CORRECTEMENT?
OUI
DECONNECTEZ LES FILS DES
BORNES DE SORTIE T1 (U), T2
(V) ET T3 (W). OL S'AFFICHE-T-IL
ENCORE?
OUI
MAUVAIS FONCTIONNEMENT
CAUSE PAR DU BRUIT?
NON
CCI DE COMMANDE OU UNITÉ
CCI DE PORTILLON EN PANNE.
REMPLACEZ LA CARTE
DÉFECTUEUSE.
SURCHARGE ( oL )
OUI
DIMINUEZ LA CHARGE
EN RESPECTANT LA
CAPACITÉ NOMINALE.
NON
AVEC L'UNITÉ EN CONDITION
D'ARRÊT, REPROGRAMMEZ n011
- n017
AU MOTIF V/f ADÉQUAT.
AVEC L'UNITÉ EN CONDITION
OUI
D'ARRÊT, REPROGRAMMEZ
n034 SUR " 0 " POUR DÉSACTIVER
LE CIRCUIT DE PROTECTION
CONTRE LA SURCHARGE
THERMIQUE DU MOTEUR.
INSTALLEZ ENSUITE UN RELAIS
THERMIQUE OU UNE PROTECTION
THERMIQUE POUR CHAQUE
MOTEUR.
AVEC L'UNITÉ EN CONDITION
NON
D'ARRÊT, REPROGRAMMEZ
n033 .
NON
VÉRIFIEZ LE MOTEUR
ET LA CHARGE.
OUI
ÉLIMINEZ LA SOURCE DE BRUIT :
• CONNECTEZ UN
PARASURTENSEUR AU RELAIS ET
AUX BOBINES DU CONTACTEUR
MAGNÉTIQUE.
• FOURNIR UN FILTRE DE LIGNE
POUR ÉLIMINER LE BRUIT SUR LA
LIGNE D'ALIMENTATION
D'ENTRÉE.
6-12