INDICATION D'ANOMALIE —
LE COURANT DE SORTIE
EST-IL SUPÉRIEUR DE 200 %
DU COURANT NOMINAL?
OC SE DÉCLENCHE-T-IL
OU LE CONTACTEUR
DU CIRCUIT PRINCIPAL
SE DÉCLENCHE-T-IL
LORSQUE L'UNITÉ EST
MISE SOUS TENSION?
OUI
VERIFIEZ LES
TRANSISTORS DE
PUISSANCE
(VOIR ANNEXE 4). LES
TRANSISTORS SONT-
ILS ENDOMMAGÉS?
NON
OC SE DÉCLENCHE-T-IL
ENCORE UNE FOIS?
MOTEUR DÉMARRE PAR DES
CONTACTS CÂBLES ENTRE L'UNITÉ
MAUVAIS FONCTIONNEMENT
CAUSE PAR DU BRUIT?
CCI DE COMMANDE OU UNITÉ
CCI DE PORTILLON EN PANNE.
REMPLACEZ LA CARTE DE
CIRCUIT DÉFECTUEUSE.
SCHÉMA DE DÉPANNAGE 6.5
OUI
NON
APPAREIL BLOQUE
NON
OU MOTEUR EN
PANNE?
NON
REMPLACEZ LES
OUI
TRANSISTORS DE
PUISSANCE
ENDOMMAGES.
OUI
NON
ET LE MOTEUR?
NON
OUI
NON
SURINTENSITÉ ( oC )
AVEC L'UNITÉ EN CONDITION D'ARRÊT,
AUGMENTEZ LE DÉLAI D'ACCÉLÉRATION
EN REPROGRAMMANT n018 OU n020 , SI
LE DÉCLENCHEMENT OC SE PRODUIT
SEULEMENT PENDANT L'ACCÉLÉRATION.
AUTREMENT, RÉDUISEZ LA CHARGE.
OUI
DECONNECTEZ LE CÂBLAGE
DES BROCHES DE SORTIE T1,
AVEC L'UNITÉ EN CONDITION
D'ARRÊT, AUGMENTEZ LE
DÉLAI D'ACCÉLÉRATION EN
REPROGRAMMANT n018 OU
n020 .
— RECÂBLEZ POUR SUPPRIMER LE
OUI
DÉMARRAGE PLEINE TENSION DU
MOTEUR.««
— REMPLACEZ L'UNITÉ AVEC UNE
AUTRE DE PLUS GRANDE CAPACITÉ.
ÉLIMINEZ LA SOURCE DE BRUIT :
• CONNECTEZ UN PARASURTENSEUR
AU RELAIS ET AUX BOBINES DU
CONTACTEUR MAGNÉTIQUE.
• FOURNIR UN FILTRE DE LIGNE POUR
ÉLIMINER LE BRUIT SUR LA LIGNE
D'ALIMENTATION D'ENTRÉE.
6-11
ÉLIMINEZ LE BLOCAGE
OU REMPLACEZ LE
MOTEUR.
T2 ET T3 ET VÉRIFIEZ
L'IMPÉDANCE DE CHARGE.
DIMINUEZ L'INERTIE
DE CHARGE.