TÉMOIN
OUI
" RUN "
ALLUMÉ?
NON
(COMMANDE PAR
L'OPÉRATEUR
NUMÉRIQUE)
OPÉRATEUR
NUMÉRIQUE
EN PANNE.
REMPLACEZ-
LE.
ENVIRON 15 VCC DE LA BORNE
SCHÉMA DE DÉPANNAGE 6.1
LE MOTEUR NE TOURNE PAS
LE TÉMOIN " CHARGE " DE
LA CCI DE COMMANDE
EST-IL ALLUMÉ?
OUI
TENSION NOMINALE AUX
BORNES L1 (R), L2 (S) ET
L3 (T)?
OUI
CODE DE PANNE
NON
INDIQUÉ SUR
L'AFFICHAGE?
NON (COMMANDE PAR LES ENTRÉES EXTERNES)
COMMANDE " STOP "
TOUJOURS ACTIVÉE?
(CIRCUIT FERME
ENTRE LES BORNES
S2 ET SC)
NON
COMMANDE " RUN "
ACTIVEE?
(CIRCUIT FERMÉ
ENTRE LES BORNES S1
ET SC)
OUI
FS(+) À LA BORNE FC?
OUI
A
VERS PAGE
SUIVANTE
6-6
NON
VÉRIFIEZ LE
DISJONCTEUR, LE
NON
CONTACTEUR MAGNÉTI-
QUE ET L'ALIMENTATION
D'ENTRÉE DU CIRCUIT.
CONSULTEZ LE
OUI
SCHÉMA APPROPRIÉ,
6.3 A 6.10
LIBÉREZ L'ENTRÉE
OUI
DE LA COMMANDE
" STOP ".
NON
ENTREZ LA
COMMANDE " RUN ".
CIRCUIT
NON
D'ALIMENTATION DE
COMMANDE DE L'UNITÉ
EN PANNE.