Problem
The device remains off, even though
it should be working
The Chlorine output cannot reach
100%
76/80
2021/02 - Indice de révision : E - Code : 29650
Possible cause
The system was turned off
The panel power supply has short
circuited
The power cable connection to the
panel is loose
The fuse protecting the main circuit
board has blown
One or both wires in the power
cable is cut.
It is not set at 100%
Electrode surfaces are dirty
(limescale, etc.)
The cell is worn out after being used
for a long time
Solution
Turn it on
Check the fuse or circuit breaker on
the electrolyser panel power line
Cut power to the panel, remove the
lid covering the panel connection
terminals and tighten the power
cable connections
Contact the after sales service for
inspection and replacement if this
proves necessary.
Inspect the cable and check
the electrical continuity using a
multimeter
Check and correct if necessary
Descale the cell
Replace the cell