3

Technical data

3.1

General data and operating conditions

General data
Conformity and approval
Conformity
CE
Protection of persons and equipment
Type of protection
Earth leakage current
Insulation of control
circuits
Insulation resistance
Protective measures
EMC
Noise emission
Interference immunity
EDKVF9338 DE/EN/FR 4.0
General data and operating conditions
2006/95/EC
Low−Voltage Directive
EN 60529
IP20
NEMA 250
Protection against accidental contact according to type 1
IEC/EN 61800−5−1
> 3.5 mA
IEC/EN 61800−5−1
Safe mains isolation by double (reinforced) insulation for the
terminals X1 and X5.
Basic insulation (single isolating distance) for the terminals
X3, X4, X6, X8, X9, X10 and X11.
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Against short circuit, earth fault (earth−fault protected during
operation, limited earth−fault protection during mains
power−up), overvoltage, motor stalling, motor
overtemperature (input for PTC or thermal contact)
EN 61800−3
Cable−guided, up to 50 m motor cable length with RFI filter:
Category C2.
Radiation, with RFI filter and installation in control cabinet:
Category C2
IEC/EN 61800−3
Category C3