Télécharger Imprimer la page

CIAT FF Manuel D'instructions page 35

Publicité

Suffocation
11
Discharge of fluid in closed spaces
Stress caused by earthquakes
12
Triaxial stress of impulsive nature due
to installation in seismic zone
Risk of device breakage due to
overstressing of thermal expansion
hindered by the effect of fixed tube
sheets
13
Increased tensions on the
components, caused by overstresses
generated by thermal expansion due
to thermal gradients higher than those
considered in the design phase
Possible damage to
8
things and people
Possible damage to
8
things and people
Possible damage to
8
things and people
- 35
Provide appropriate systems
to collect gas escaping from
the equipment or ventilation
systems of adequate capacity
for the fluid present in the
system.
The sizing of the exhaust gas
pipes connected to safety
valves must be carried out by
expert personnel in
compliance with mandatory
regulations
The end user must have an
external technical office
determine the stability of the
equipment for loads caused
by earthquakes.
Installation of a thermal
probe / thermostat in order to
directly verify / check the
working temperature range to
avoid exceeding the thermal
gradients considered in the
design phase
Have qualified personnel
carry out the fluid filling
and emptying operations
according to mandatory
regulations
By the end user
By the end user