ATTENTION
Damage to sensors
Opening the volume flow suddenly can damage the sensor.
Check the filter (if fitted) regularly and replace if dirty.
Open the ball valves slowly.
Hydraulic connection with accessories
The cold water is connected according to DIN 1988. It must not be possible to
lock the safety valve. The mains water station must always be operated via a
buffer tank.
The integration of a flow-through expansion vessel on the potable water side
(cold inlet side) is recommended.
The first step is to open the most distant tap on the potable water side. Fill the
system slowly with potable water and ensure that it is carefully vented.
Venting on the heating side is carried out by the integrated manual air vent.
Connection to the system
KW
Cold water
WW Hot water
Hydroflow XS-M
PVL
Buffer lead
PRL
Buffer return
Reflex Hydroflow Mains Water Station — 20.12.2023
Hydroflow L-XL
Installation
English — 37