Special options
Parametrisation and commissioning
To change from operation to parametrisation mode
push the "ENTER" button
for minimum 3 seconds.
If password protected: type password and push
Back over to menu "Save" and exit.
Menu
Function
Menu 1
DE, EN, FR
Select language: German, English, French
Menu 2
no function – menu skip
Menu 3
no function – menu skip
Menu 4
Unit sensor
Select physical unit
Menu 5
Range
Adjust the measuring range
Menu 6
no function – menu skip
Menu 7
Output V, mA
Select output signal as V or mA
Menu 8
Output range
Adjust output range
Menu 9
Sensor error
Select signal at sensor error
Menu 10
Output
Select signal output behaviour
Menu 11
no function – menu skip
Menu 12
no function – menu skip
Menu 13
no function – menu skip
Menu 14
no function – menu skip
Menu 15
no function – menu skip
Menu 16
Output Ex-i (option, only at ...Cos-P-...-A)
Select lower output signal: 0 mA resp. 4 mA
(0...20 or 4...20 mA)
Menu 17
no function – menu skip
Menu 18
Zero point compensation
After short circuit the pressure nipples P+/P−
the sensor gets a zero point calibration
Menu 19
Display function
Select display settings
Menu 20
Password
Select password protection
Menu 21
Save and exit
Select: save data, factory setting,
discard or back to menu
Menu 22
Set offset
Add/subtract offset from measure value
Menu 23
no function – menu skip
Menu 24
Attenuation
Damping the output signal (signal filter)
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
ExCos-P...-A
...-CT
...-OCT
...-VA
Operation → Parametrisation
.
push
for min. 3 s
Indication
ENTER
DE, EN, FR
English
Deutsch, English, Francais
unit sensor
Pa
Pa, mbar, inH
O
2
range
−25...100 Pa
adjust lower limit
output V / mA
mA
V, mA
output range
4...20 mA
adjust lower limit
sensor error
10 V /20 mA
10 V /20 mA or 0 V / 0 mA
output
increasing
increasing, decreasing
output Ex-i
0...20 mA
adjust lower limit
set zero point
yes
no
display function
on illuminated
on, on illuminated, off
new password
yes
no
save and exit
save data
save data, factory setting, discard, back to menu
set offset
0.00 Pa
attenuation
0
www.schischek.com
...-OVA
E X P L O S I O N P R O O F
E X P L O S I O N P R O O F
Select
Next indication
ENTER
range
−25...25 Pa
adjust higher limit
output range
4...20 mA
adjust higher limit
output Ex-i
0...20 mA
adjust higher limit
password
0000
Example:
Menu language
English
Range
−25...+25 Pa
Output
4...20 mA
Output Ex-i
0...20 mA
Select
ENTER Next menu
ExCos-P_en
V02 –
4-Jul-2016