ExBin-P...
Special options
Continue Parametrisation
Menu
Function
Menu 8
no function – menu skip
Menu 9
no function – menu skip
Menu 10
no function – menu skip
Menu 11
no function – menu skip
Menu 12
time
Select bypass (AUB) time
Menu 13
display setting
Select display
Menu 14
Zero point compensation
Sensor's calibration for
its installation position
Menu 15
security
Select password protection
Menu 16
save
Select: save data, discard,
back to menu, factory setting
* for ...Bin-P-...-2 only (2-stage)
** adjustable in professional mode only (menu 1)
Menu 1 "pset" – Preset
For some applications you can select presetting to ease parametrisation. Besides fan belt
(„FAN") and filter monitoring („FILT") the professional mode („PRO") is available for further
applications.
Fan speed monitoring
The preset "FAN" hides menu 5 ("hysteresis") and 6
("mode") during parametrisation. The corresponding
values are set automaticly.
−
state
output
switch 1
red
state
output
switch 2
red
(optional)
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
ExBin-P...-2
...-CT
...-OCT
Indication
ENTER
M
∆p
+
setpoint 1
setpoint 2
Hysteresis
Hysteresis
www.schischek.com
...-VA
...-OVA
Select
ENTER
enter seconds for AUB
on, off
enter password
Yes, no, menu, dset (default setting)
Professional mode
Filter monitoring
normal
state
green
output
switch 1
normal
state
green
output
switch 2
(optional)
E X P L O S I O N P R O O F
Next indication
Select
(operation mode after "save")
When this mode is selected the switching properties
can be set at will per menu 5 ("hysteresis") and 6
("mode") acc. to requirements.
The preset "FILT" hides menu 5 ("hysteresis") and 6
("mode") during parametrisation. The corresponding
values are set automaticly.
∆p
−
+
setpoint 1
setpoint 2
normal
green
Hysteresis
Hysteresis
normal
green
ENTER Next menu
red
red
ExBin-P_en
V02 – 18-Oct-2016