Menu → Configurations → Fonctions → Bobine de réactance
P1712 - Bypass de la cellule V1
P1713 - Bypass de la cellule V2
P1714 - Bypass de la cellule V3
P1715 - Bypass de la cellule V4
P1716 - Bypass de la cellule V5
P1717 - Bypass de la cellule V6
P1718 - Bypass de la cellule V7
P1719 - Bypass de la cellule V8
P1720 - Bypass de la cellule V9
P1721 - Bypass de la cellule V10
P1722 - Bypass de la cellule V11
P1723 - Bypass de la cellule V12
Plage réglable :
Description :
It defines whether the respective cell should be removed from the system (option > 0).
The option 1 should be used when the corresponding cell is replaced by a mechanical bypass cell.
Option 2 must be used to manually actuate the automatic bypass relay of the cell.
Option 3 is read-only. Indicates that the respective cell was automatically removed from operation due to a
manageable fault.
Option 4 is read-only. Indicates that the respective cell was automatically removed from operation, because it
was linked in parallel (P1892) with another cell that was bypassed.
Once the parameter is set to 1, 2, 3 or 4, the respective cell can operate again as soon as the user resets the
parameter to 0 (Désactivation).
Refer to P1500 (Dérivation automatique).
ATTENTION
Option 1 must be used after the user has physically verified that the cell in question is assembled in
the set and that it has the bypass system.
✓
REMARQUE !
Ce paramètre est modifiable uniquement avec le moteur à l'arrêt.
0 à 4
Table 5.77 – Bypass de la cellule V12
P1723
0
Dérivation mécanique d'élément de pile
1
2
Activation manuelle du relais de dérivation
Dérivation automatique après une erreur gérable
3
Dérivation automatique par association parallèle
4
DESCRIPTION DÉTAILLÉE DES PARAMÈTRES
Paramètre D'usine :
Fonction
Désactivation
0
MVW3000 | 5-117