Trouble shooting
PROBLEM
The operator neither opens nor closes
The operator opens but doesn't close
The operator closes but doesn't open
The operator does not carry out the auto-
matic closing
The transmitter doesn't work
The operator inverts the direction of travel 7-18
Only one transmitter works
The photocell does not work
The LED flashes quickly
Il LED stays on
The operator does not fully complete cycle
Cannot balance the arm
The operator does not decelerate
The operator does not run on the emer-
gency batteries
The operator is slow when starting
Reference
CHECKS
Checks
1-2-3-4-6-8-18
1 - Lock the inspection hatch using the key and check
the release lock
4-7-10
2 - 2 - Deactivate the Maintained action function via
4-7-9
Dip-switch
3 - 3 - Check power source and fuses
11-12-13
4 - 4 - The N.C. safety contacts are open
6 - 6 - Deactivate the master-slave function
2-14-16
7 - 7 - Check balancing and tighteness of springs
8 - 8 - Deactivate the Obstacle detection function via
Dip-switch
22
9 - 9 - Check opening endpoint
12-23-24
10 - 10 - Check closing endpoint
4
11 - 11 - Activate the Automatic Closing function via
Dip-switch
13
12 - Check for the proper direction of travel
7
13 - Check the command devices
14 - 43 - Cut off and bring back power to card or
7-15
check the TOP/TAM jumper on the AF43S card
7-15
15 - 15 - Check the Arm length/Applied Accessories
ratio
8-25-26
16 - 16 - Memorise the new radio code
18 - Adjust sensitivity
7
22 - Insert or duplicate the same code in all transmit-
ters transmitters
23 - Activate the photocell via Dip-switch
24 - Connect the photocells in series and not in paral-
lel fashion
25 - Check the batteries
26 - Respect the polarities when powering up the
photocells