8.3
Installation
WARNING!
Risk of injury due to improper installation!
Failure to observe the tightening torque value is dangerous due
to the risk of damage to the device.
▶ Use an open-end wrench for installation, never a pipe
wrench.
▶ Observe tightening torque (see "Tab. 8").
Dirt trap for devices with approval according to EN 161
According to EN 161 "Automatic shut-off valves for gas burners
and gas appliances", a dirt trap, which prevents the penetration
of a 1 mm test pin, must be installed upstream of the valve.
8.3.1
Installing the body
Welded connection
→ Weld or bond valve body in pipeline system.
Other body variants
→ Connect valve body to pipeline.
14
All manuals and user guides at all-guides.com
8.3.2
Fig.5:
→ Check seal and replace if required.
Risk due to incorrect lubricants!
Unsuitable lubricant may contaminate the medium. There is a
risk of explosion in oxygen applications!
▶ For specific applications, e.g. oxygen or analysis applications,
→ Before re-installation, grease nipple thread of the actuator
NOTE!
Damage to the seat seal or seat contour!
▶ When installing the actuator, the valve must be in the open
English
Type 2300
Structure and function
Install actuator (welded connection)
Seal
WARNING!
use approved lubricants only.
(e.g. using Klüberpaste UH1 96-402 from Klüber).
position.
Seal