Technical Characteristics; Transport And Storage; Products And Accessories - salmson ALTI-V ELINOX-V 36 Manuel D'installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENGLISH
1. GÉNÉRAL
Application
• The essential role of the booster is to pressurize a water distribution
network in which the pressure is too low or non-existent.
ALTI-V for clear, non-aggressive liquids (drinking water, glycolated
water, etc.).
ELINOX-V for aggressive liquids (seawater, de-ionized water, etc.)
Water may be supplied to the module either from a town water sys-
tem (version "V") or from a storage tank (version "B").

1.2 Technical characteristics

{
• Max. operating pressure
• Max. water temperature, ALTI-V
• Max. water temperature, ELINOX-V
• Max. ambient temperature
single-phase 50 HZ : 230 V (option)
• Power supply
single-phase 60 HZ : 220 - 240 V (option)
three-phase 50 Hz
three-phase 60 Hz
2. SAFETY
Read these instructions carefully before installing and starting up. Pay
special attention to the points concerning the safety of the equip-
ment for the intermediate or end user.
2.1 Symbols and instructions of the manual
Safety precautions in these operating instructions which, if not
followed, could cause personal injury are indicated by the
symbol.
Safety precautions warning of danger due to electricity are
indicated by the symbol.
The following symbol is used to indicate that by
ATTENTION !
ignoring the relevant safety instructions, damage
could be caused to the pump/machinery and its functions.

3. TRANSPORT AND STORAGE

When the equipment is delivered, check that it has not been dama-
ged in transit. If any defects are found, make the necessary arran-
gements with the carrier.
If the equipment delivered is to be installed at
ATTENTION !
some later time, store it in a dry place and protect
it from impacts and all outside influences (moisture, frost, etc.).
Handle the equipment with care.

4. PRODUCTS AND ACCESSORIES

4.1 Description of ALTI-V & ELINOX-V with automat (see Fig. 1a)
4.1.1 Product
1
- Control and automation cabinet
2
- Pressure switch for automatic control of pumps
3
- Pressure gauge
4
- Dry-running pressure switch (version "V")
5
- MULTI-V multi-stage vertical pumps
6
- Air bleed-filling plug
7
- Support and attachment frame
8
- Suction pipe
9
- Discharge pipe
Nota : Each pump has isolating valves on the suction and check and iso-
lating valves on the discharge.
4.1.2 Automat control cabinet (CA)
• Fully automates the booster.
• Sealed, IP 559 protection.
• Thermal protection of motors factory-adjusted to current rating
marked on motor data plate.
: 16 bars
: + 60° C
: + 70° C
: + 40° C
: 230/400 V
: 220/380 - 230/400 V (option)
13
• Outside module safety and power switch (can be locked).
• Closed by key lock.
On front (see Fig. 2a)
1
- ON indicator light
2
- Dry-running indicator
3
- Fault indicator (one per pump)
4
- ON indicator light (one per pump)
5
- Switch (one per pump), three-way: AUTO/STOP/MANUAL
(while pressed)
Inside (see Fig. 2b)
1
- 24-230V safety transformer.
2
- Contactor (one per pump) with motor connection terminals
3
- Terminal block for connection of external units (pressure
switches, float switch, fault remoting)
4
- Magneto-thermal circuit-breaker with motor current
adjustment wiper (and reset button)
5
- Adjustable industrial automat
4.1.3 Automatic operation pressure switch (see Fig. 3)
This pressure switch is used for automatic starting and stopping of the
pumps; it has a neutral range.
1
- High pressure (PF) adjustment thumbwheel.
2
- Scale with slide for setting the value of the high pressure (PF).
3
- Nomograph giving the difference adjustment value (behind
the cover).
4
- Difference adjustment thumbwheel (reached by
withdrawing the cover).
PF:
High pressure or pump stopping pressure
Pf:
Low pressure or pump starting pressure
PF = Pf + Difference (PF - Pf)
4.2 Description of electronic ALTI-V and ELINOX-V (see Fig. 1b)
4.2.1 Product
1
- Electronic automation cabinet
2a
- Control pressure switch PR1 in two-pump version
2b
- Control pressure switch PR2 in two-pump version (in three-
pump version, automatic operation pressure switch with
neutral range) (see Fig. 1a, item 2)
3
- Pressure gauge
4
- Dry-running pressure switch (version "V")
5
- MULTI-V multi-stage vertical pumps
6
- Filling plug
7
- Support and attachment frame
8
- Suction pipe
9
- Discharge pipe
Note:
Each pump has isolating valves on the suction and check and isola-
ting valves on the discharge.
4.2.2 Electronic control cabinet (CE)
• Fully automates the booster.
• Sealed, IP 54 protection
• Thermal protection of motors factory-adjusted to current rating
marked on motor data plate.
• Outside module rotary safety and power switch.

Publicité

Table des Matières
loading

Table des Matières