Tab. 2:
Functions
of the inputs
EN
38
Function types
Emergency mode
In the event of a power failure or when a connected fire alarm system is triggered,
the motorised lock moves into the closed position immediately via the internal
emergency power supply if the lock was previously in the open or daytime
position. If the lock was in the closed position, nothing changes on the status
externally. If an "open" command is given immediately after a power failure
during the emergency power supply (approx. min. 10 sec.), it has no effect.
Functions of the inputs
All 6 inputs (terminal 5 to 16) can be activated by connecting the relevant
2 terminals or by applying a systeminternal ground potential (GND) on the
relevant uneven terminal (e. g. GND on terminal 5 to activate the "impulse"
command).
inputs
Functions
Impuls X8 (6 – 5)
The motorised lock moves to open position and returns to
drive /e-drive
the closed position after the open time has elapsed. While
access/e-access
the lock is in open position, the door drive (door drive
release) is switched. This input must be used to switch the
door to permanently open (ventilation).
If an impulse of 1.5 sec. on door drive is desired, set DIP5 ON
and DIP6 OFF (see Function DIP switch).
Day X9 (8 – 7)
Motorised lock moves into daytime position without
drive/access
actuation of the door drive relay (bolt extends 5 mm and
the tilt latches are rigid => lock is not locked). This results in
"quick" opening under 1.0 sec. after the open impulse, e. g.
X8, has been issued. Should preferably be used for day/night
mode switching (timer) with daytime function/day position.
Important The radar input is only active if day is active (e. g.
connection radar external => switched off in night mode).
Abkürzungen