Tab. 2
Functions
of the inputs
(continuation)
Abkürzungen
inputs
e-drive / e-access
Radar X10
(10 – 9)
Lock X11
(12 – 11)
Permanently
open X12
(14 – 13)
Door contact X13
(16 – 15)
Functions
With edrive/ eaccess, the panic opposite side is motorised
engaged while "day" is active.
Motorised lock moves into open position and switches
door drive for 1.5 sec. if daytime or permanently open
is pressed (day mode timer). If the motorised lock was
already open (e. g. 1413 permanently open bridged), a new
door drive impulse (1.5/5.0 sec.) is generated. Radar input
is only active if day or permanently open is active!
Motorised lock can not be opened by any open commands
(AMOK). The lock now moves immediately into the closed
position. Once the locking input is open again, the lock
returns to the previously set status, e. g. permanently open.
Application: Building sectors with an impulse for locking
the lock without intervention in the building management.
All input wirings remain in place!
Motorised lock moves into open position without actu-
ating the door drive relay. Should preferably be used for
day/night mode switching (timer) with permanently open
setting => lock unlocked, tilt latches soft. Important The
radar input is only active if permanently open is active (e. g.
connection radar external => switched off in night mode).
Connection of a door contact (Reed contact) to the
sequence control. If the door is closed, terminal 15 and 16
must be bridged. If the door is opened, the motorised lock
moves immediately into the closed position. If the door is
opened (terminal 15 and 16 disconnected) and the bolt is
extended due to tampering on the control latch, the motor
retracts the bolt again to prevent the door from hitting the
frame with the extended bolt. If no external door contact is
present, the terminals 15 and 16 must be bridged (delivery
state)!