The default password is 2967. Select Set User Password to change the password:
When the first digit blinks, change the value by using the up/down keypad arrows to increase or de-
crease the number
Use the left/right keypad arrows to move from one digit to the next.
When the desired value has been set, press Enter to validate it and exit the editing mode.
Contact Honeywell technical support for help with
lost passwords at 1-800-563-2967.
From the main menu screen scroll to the Config menu. This menu allows the relay configuration to be set, the
AP broadcast mode and to select from four separate manufacturers for the given controller.
When Relay Configuration is selected, two further options to configure the relays are available: The first
screen, Failsafe, appears allowing the failsafe to be activated for all relays using the Enter keypad button. This
function inverts relay operation to be normally energized. If power is cut, the relay will activate the connected
device (ex. a light).
Scrolling to the right displays the "Silence" screen that enables or disables the silence option for each relay,
using the Enter keypad button.
The fourth screen in the Config menu allows a definition of a day and a week to be programmed.
Day and Week definition allows hours (time frames) to be defined for Daytime and Working Days respectively.
Remember, the controller uses a 24-hour clock (0:00
to 23:59). Any time changes (e.g., for Daylight Sav-
ings Time) must be made manually or through BAC-
Net time synchronization (BACNet module required)
62
6. Config
Relay Configuration
AP Brdcst: auto
Honeywell
Relay Config
-Failsafe-
All relays
inactive
Relay Configuration
-Silence-
1
2
3
4
Dis ena
dis
dis
6. Config
Day definition
Week definition
Day definition
-Daytime-
Sta:
08:00
End:
17:00
Week definition
-Working Days-
Sta:
Monday
End:
Friday