Detection Menu
The detection menu (available only for devices with addresses between 1 and 96)
displays the detection range (scale: 0‐100.0) and the unit of measurement (unit: %)
for the selected component. If a transmitter uses the Modbus protocol, the detec-
tion parameters are automatically defined during network configuration and are not
editable. Vulbus protocols must be manually defined by the programmer.
The detection scale is between 0 and the maximum value (0.00) and the unit of
measurement is either ppm or percent (% for oxygen and
% LEL for combustibles).
The detection menu is not available for the VA301R or VA301AP.
1. Tx info 001
-Detection-
Scale:
0-0.00
Unit:
%
Programming or modifying the scale range or unit:
•
Use the arrows to move the cursor to the scale or unit option
•
Press Enter and use the arrow to increase or decrease the value
•
Press Enter when the desired value is obtained
Display Menu
This option allows a specific label or name to be assigned to the selected compo-
nent (transmitters, relay modules, annunciators). Up to 20 characters, including
spaces, can be used in the label (example: BOILER ROOM). The default Modbus
transmitter labels are composed of the component (or transmitter) name, sensor
type and address.
Vulbus transmitter labels contain 20 blank characters (spaces).
1. Tx info
-Display-
Edit
(20 char.max)
S301-D2 CH4 Ad001
31
001