3. Top right portion contains the source, which defines what device or group
of devices the Event will be based on. The list provides the following op-
tions:
Option
GrAll
Includes all transmitters (see note)
GR _ _ _
Includes only the devices in the specified group (see note)
Includes only the specified transmitter (connected to the controller)
Tx000
Includes only information gathered between the specified times. Se-
lecting clock sets a condition that is applied only between the start and
end time frame. It is possible to set one condition screen to specific
Clock
parameters and the second to clock, which means that the specified
condition will trigger an event only if it occurs during the set time pe-
riod.
Note: Clicking on the magnifying glass to the right of a Group number on the display opens
a view of the Group for consultation or editing. Press Esc to close the group view
and return to the Event condition screen.
4. Bottom right portion contains the operand, which defines what device or
group of devices on which the Event will be based. The list provides the fol-
lowing options:
Option
OFF
Used for status on binary inputs (ex.: used with 301ADI)
ON
Used for status on binary inputs (ex.: used with 301ADI)
Bases trigger on maintenance alarm, communication failure or device
Fault
failure
If the chosen device or group has an Alarm A or Alarm 1, an event will
Alrm A
be triggered.
If the chosen device or group has an Alarm B or Alarm 2, an event will
Alrm B
be triggered
If the chosen device or group has an Alarm C, an event will be trig-
Alrm C
gered.
43
Honeywell Internal
Description
Description