Number of Sensors/Monitors
The number of units required to protect an area is determined by the unit's detec-
tion radius, which depends on the gas detected, as shown in the following table.
Gas Detected
CO
Carbon monoxide
NO2 Nitrogen Dioxide
Others
Sensor/Monitor Heights
Detected Gas
CO
Carbon Monoxide
*NO2
Nitrogen Dioxide
CL2
Chlorine
H2S
Hydrogen Sulfide
O2
Oxygen
SO2
Sulfur Dioxide
R11
Refrigerants
R114
Refrigerants
R22
Refrigerants
R123
Refrigerants
R125
Refrigerants
R134A
Refrigerants
R404A
Refrigerants
R407C
Refrigerants
R410A
Refrigerants
R507
Refrigerants
R1234yf
Refrigerants
R1234ze Refrigerants
1233zd
Refrigerants
R514a
Refrigerants
10
Surveillance
Radius
15 m (50 ft.)
15 m (50 ft.)
7 m (23 ft.)
Relative Density
(air = 1)
0.968
1.58 (cold)
2.5
1.19
1.43
2.25
5.04
5.9
3.11
5.27
4.14
3.52
3.43
3
3
3.43
4.00
4.00
5.50
5.00
Area Covered
707 m2 (7610 ft
)
2
707 m2 (7610 ft
)
2
154 m2 (1658 ft
2
)
Installation Height
1 - 1.5 m (3 - 5 ft.) from floor
30 cm -1 m (1-3 ft.) from ceiling
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
1 - 1.5 m (3 - 5 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor