If ManSW#1(or #2) was selected at the previous step
this screen will only have 2 options: Open or Closed.
Set to Open if the output is set to Normally Closed, or
to Closed if the output is set Normally Open.
When you have selected the option, and pressed enter, the field is disabled and you can proceed to the next
screen. Use the arrows to move ahead one screen.
The third event screen lets users specify the actions linked to the event. The screen displays REL #1 (the de-
fault value).
Press enter to enable the field and use the arrows to scroll through the options:
REL #1: (through REL #4) Triggers the devices connected to the selected relay
OUT #1: (through OUT #3) Triggers the devices connected to the selected Output
BUZZER: Triggers the audible alarm for this event
---:
Displays the EraseALL screen. When "Yes?" is selected from the Event #1 menu, all configuration
data for events will be erased.
Note that when "---" is selected at any other event number, the EraseALL screen does not appear
and the data for the active event number will be erased (and events will change numbers, moving up
one).
When you have selected the option, and pressed enter, the field is disabled and you can proceed to the next
screen. Use the arrows to move ahead one screen.
The final screen, RESET, lets users specify that an event will remain active, even after it has returned to nor-
mal.
Press enter to enable the field and use the arrows to scroll to Y?.
Press enter once again to activate the Reset function.
The Reset key on the front panel lets you deactivate the event
Note:
Using the SetRelay Menu
The SetRelay menu lets users specify whether the relay for the event will be in failsafe mode and whether the
Silence button on the user interface (front of housing) will be enabled for this event.
Press enter to select the menu and use the arrows to scroll through the options:
FAILSAFE? Puts the relay in Failsafe mode (the default setting is no failsafe).
Silence
Enables the Silence button function of the user interface for this event.
When you have selected the option, and pressed enter, the field is disabled and you can proceed to the next
screen. Use the arrows to move to the next menu.
93
Event# 1
REL #1
EraseALL
No?
Event# 1
RESET N?
Menu
SetRelay

Publicité