301-Adi Objects; 301-R8 And Aa96D-Rm8 Objects - Honeywell 301 Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

301-ADI Objects

Group
Property
Object_identifier
Object_type
Enumerated
Event_state
Enumerated
Object_name
Character
string
Out_of_service
Boolean
Present_value
Real
Reliability
Enumerated
Status_flags
In_alarm
Boolean
Fault
Boolean
Overriden
Boolean
Out_of_service
Boolean
Units
Enumerated

301-R8 and AA96D-RM8 Objects

Group
Property
Object_identifier
Object_type
Enumerated
Event_state
Enumerated
Object_name
Character
string
Out_of_service
Boolean
Polarity
Enumerated
Present_value
Real
Reliability
Enumerated
Status_flags
In_alarm
Boolean
Fault
Boolean
Overriden
Boolean
Out_of_service
Boolean
118
Data Type
Required
Storage
1
R
R
R
R
R
R
O
R
R
R
R
R
Data Type
Required
Storage
1
R
R
R
R
R
R
O
R
R
R
R
BACnet
type
writeable?
2
C
N
(Modbus address + channel number) *256- 255, where channel
number is 1 to 16. For example analog input 7 from a 301ADI at
address 097 will appear as 26369 or 0x6017
C
N
Analog_input (0)
R
N
Not meaningful
N
N
"adXXX.Al.CC" where CC is the channel number from 1 to 16 and
XXX is the Modbus address
R
N
FALSE
R
N
Reading from 301C, mA by default. Scaling in the 301C is supported
R
N
Not meaningful
R
N
Not meaningful
R
N
"false" (0)
R
N
"false" (0)
R
N
"false" (0)
N
N
mA(02) by default. Reconfiguration in the 301C is possible. New
units may not propagate unitl power cycle
BACnet
type
writeable?
2
C
N
RelayModbus + Modbus ddress *256+7. For relay in a 301R at
Modbus address will appear as 24331 or 0x5F0B.
C
N
Binary_input (3)
C
N
Normal (0)
N
N
"VA301R AdXXX.relR" where XXX is the Modbus and R is the relay
number
C
N
FALSE
C
Always normal (0)
R
N
True if and only if the relay is driven by an event
C
N
No_fault_detected (0)
C
N
Always "false" (0)
C
N
Always "false" (0)
R
N
Always "false" (0)
R
N
Always "false" (0)
Value
Value