4
TECHNISCHE DATEN
Operating voltage
Power consumption
Output current (to valve)
Operating temperature
Interference resistance
Interference emission
Inputs
Sensor input
temperatur range
resolution
precision
1 standard signal input
resolution
input impedance (4 - 20 mA)
input impedance (0 - 10 V)
Output
PWM output
Controller
Control algorithm
Scan time T
A
Amplification factor K
Reset time T
N
Scaling
Housing
Cable outlet
System of protection
Material
Dimensions (WxHxD)
Order no.
1)
Calibrated to 1 m conductor length and 0.5 mm² conductor cross-section.
24 V DC
max. 0.3 W (without proportional valve)
max. 1.0 A
- 10 °C ... + 60 °C / 14 °F ... 140 °F
to EN50082-2
to EN50081-2
PT100
- 50 °C ... 150 °C / - 58 °F ... 302 °F
0.25 °C or 0.45 °F
1.5 °C bzw 2.7 °F
4 - 20 mA / 0 - 10 V, adjustable
10 Bit
< 200 Ω
> 300 kΩ
24 V - pulse width modulated
PI control
50 ms
0,00 - 10,00 %/K
p
0,1 - 200,1 s
-50 °C ... 150 °C or -58 °F ... 302 °F
rotatable in 90° steps
IP 65
polyamide
54 x 54 x 61 mm
143 571
1)
1)
8625-2 Standard - 7