From K
and T
crit
crit
following table.
Parameter setting according to Ziegler and Nichols:
Controller type
P
PI
The adjustment rules of Ziegler and Nichols have been determined for P members
with first order time increase and dead time. However, they apply only for
controllers with disturbance behaviour and not for those with command behaviour.
30 - 8625-2 Standard
All manuals and user guides at all-guides.com
, the controller parameters can then be calculated using the
Parameter setting
K
= 0,5 K
p
krit
K
= 0,45 K
T
p
krit
N
-
= 0,85 T
krit