Malfunctions

Fig. 20: Control air connection
All manuals and user guides at all-guides.com
Upper control air connection
(for CFB and CFI)
Lower control air connection
(for CFA and CFI)
12
malfuncTiOns
Malfunctions
cause / remedial action
Actuator
Control connection interchanged*
does not
CFA:
Connect lower control connection
switch
CFB:
Connect upper control connection
CFI
Upper control connection: Close
Lower control connection: Open
* see "Fig. 20"
Control pressure too low
See pressure specifications on the type label.
Medium pressure too high
See pressure specifications on the type label.
Valve is not
Medium pressure too high
sealed
See pressure specifications on the type label.
Control pressure too low
See pressure specifications on the type label.
Flow rate
PTFE diaphragm bulging
reduced
Replace diaphragm.
english
25