8 Configuration
Name
Frq. monitoring upper min. threshold trip. time (Un-
derfrequency, maximum time)
Frq. monitoring lower max. threshold trip. time
(Overfrequency, maximum time)
8.7
Activating of the Rapid Shutdown DC discharge
function
The DC discharge function should be activated if an additional DC switch-disconnector between the
inverter and the PV array is available. The additional DC switch-disconnector disconnects the PV
array in the case of a rapid shutdown.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.2 "Changing Operating Parameters", page 39).
Procedure:
• Set the parameter Rapid Shutdown Mode or Op.RssOpMode to On.
42
STPTL-US-10-IA-xx-22
SMA Solar Technology America LLC
Value/range
Default value
0.1 s to 1000 s
0.1 s to 1000 s
Installation Manual
0.16 s
0.16 s