4 Product Overview
An electric arc with a power of 300 W or greater must be interrupted by the AFCI in the time
specified by UL 1699B. A detected electric arc causes the inverter to interrupt feed-in operation. In
order to restart feed-in operation, the feed-in operation must be activated manually. If the
installation conditions allow it, you can deactivate the arc-fault circuit interrupter.
Q on Demand 24/7
The inverter can supply reactive power by means of Q on Demand 24/7 covering the entire unit
circle around the clock (for details on the configuration refer to the Technical Information
"Integrated Plant Control and Q on Demand 24/7" at www.SMA-Solar.com).
Integrated Plant Control
The inverter can display the Q(V) characteristic curve specified by the grid operator by means of
Integrated Plant Control without measuring on the grid-connection point. The inverter can
automatically compensate equipment installed between the inverter and the grid-connection point
after having activated the function (for information on the system configuration refer to the Technical
Information "Integrated Plant Control and Q on Demand 24/7" at www.SMA-Solar.com).