Software Diagnosis - Aventics DDL Mode D'emploi

Bus coupler for series vs cl03/cl03-xl
Masquer les pouces Voir aussi pour DDL:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 91
76
AVENTICS | DDL, CL03/CL03-XL | R402003658–BDL–001–AE
Commissioning and Operation
No DDL communication
Diagnostic data of the VS
Within the DDL line, each DDL participant's plug connection and
each increase in cable length lower the voltage. The bus coupler
works with an operating voltage of 24 V DC and has been
designed for the following tolerance ranges:
Table 16:
Thresholds of the supply voltages
Voltage at X72
Electronics voltage
Sensor voltage
Valve voltage
U BYTE 1– U BYTE 4
1)
Adjustable via S6.2, see Tab. 19 on page 78.
Possible causes for a display of missing DDL communication
are:
W
Data rates set for the bus couplers are not the same.
W
There are gaps in the addressing.
W
The same address was assigned to 2 modules.
W
Address 0 and 1 to 14 have been assigned simultaneously.
W
The configuration has been changed during operation.
W
The configuration of the inserted modules is incorrect.
W
Problem with the internal data communication
(e.g. defective modules).
W
Incorrect initialization

7.3.2 Software diagnosis

The software in the controller monitors the connected VS. To do
this, the bus coupler transfers the diagnostic data to the
superior module, which provides it to the controller.
The diagnostic data of the valve system is located in the
diagnostic data section in accordance with the DDL address. If
the address 0 (automatic addressing) is set, the VS will act like
a valve unit.
The length of the diagnosis area is 1 byte plus the set output
data length in bytes (see "Setting the output data length for
valves" on page 70).
U
[V]
U
min
max
19.2
28.8
1)
21.6/20.4
26.4/27.6
[V]
1)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cl03Cl03-xl

Table des Matières