4.3 Connecting the additional limit switch
In the standard variant, the actuator has 2 additional limit switches (for 90º range of
motion). Connect these as follows.
Work steps:
Remove the position indicator from the cover.
Use a screwdriver to loosen the cover screws.
Lift the cover off.
DIN plug option:
Loosen the plug screw and insert the connection leads through the plug.
NOTE
Connect these as follows.
Normally closed (NC)
Switch
Connector
FC1
4 and 8
FC 2
6 and 9
Tighten the screws of the plug after connecting power as described above.
Reinstall the plug.
Set the cover in place and screw it tight.
Reinstall the position indicator
ATTENTION!
the ISO 20 cable connector must be used for wires from 5 mm to
12 mm.
Do not move the coupling knob by hand; it is moved only by the
electrical actuator.
Normally open (NO)
Switch
Connector
FC1
4 and 5
FC2
6 and 7
3003 - 15