Convection+Humidif.Combi Direct 5x2/3 GN / 7-11-20 x 1/1 GN / 7-11-20 x 2/1 GN
2.1 CONNECTING TO THE FLUE
The appliances are provided with a flue for eliminating the products of combustion.
This flue must be connected as illustrated in Figures 2.1 – 2.1A as established by the installation
rules.
2.1A Natural fumes evacuation type B23:
Connection is made to an effective natural draught flue by means of a wind proof fitting, not part
of the oven's standard fittings, with discharge of the combustion fumes directly into the
atmosphere.
2.1B Forced fumes evacuation type a3:
The supply of gas to the appliance must be interlocked directly to the forced evacuation system
and must shutdown whenever the latter's rate of flow drops below the values prescribed by the
current installation standards.
It should only be possible to restore the supply of gas by hand.
If the appliance is installed under an extractor, the end part of the appliance's exhaust gas pipe
should be at least 1.8 m from the surface on which it stands.
The exhaust pipe's outlet section should be positioned inside the base perimeter of the extractor.
3 x d
GAS POWERED OVENS
(Fig. 2.1)
(Fig. 2.1A)
Fig. 2.1
d
39
Fig. 2.1A