System Configuration Password 21100 (100) - DAB EEG0,75T3 S Serie Instructions De Mise En Service Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 38
11.5
SYSTEM CONFIGURATION TECHNICIAN PASSWORD: 21100
!!! ATTENTION: THESE PARAMETERS MAY BE MODIFIED ONLY BY QUALIFIED PERSONNEL OR THE DAB
SERVICE PERSONNEL! !
[100] Language
Menu language.
[101] Type of system
1) Booster sets
2) Circulators
[102] Type of operation
System operation.
1) P-c, Constant pressure.
2) Dp-c, Constant diff. pressure.using:
- a differential transducer connected
to the terminals: 1 - 2 - 3.
- two relative transducers TRP1 –
TRP2 connected to the terminals: 1-
2-3 for the delivery pressure, 1-5-6
for the suction pressure.
3) P-c, as analog input 0-10V (AN1).
[103] RS485 address
Setting the number of the node in the
modbus supervision network.
[105,106 and 107] Motor 1, 2 and 3
Thermal Protection
Threshold of intervention for reached
current limit, on Motor 1, 2 and 3.
SET THE MOTOR DATA PLATE
VALUE.
[108] Pressure Transducer full-scale
Full-scale
value
transducer in bar.
[109] Load loss compensation
Automatic increase in bar of the
Reference Pressure, for switching on
pumps in cascade mode.
Access page to sub-menus by selecting:
100: System settings
200: Inverter
300: Input/Output
To move from one sub-menu to the other use the arrow keys.
To select the sub-menu (100 / 200 / 300) the respective symbol must be next to
the key
Sub-menu 100 – System Settings
0.0 – 150.0 A
of
the
pressure
0.0 – 100.0 bar 10.0 bar
ENGLISH
which must be pressed to confirm.
Field
Default
Italian
English
Italian
French
German
Spanish
Booster
001 - 255
001
0.0 A
0.0 – 1.0 bar
0 bar
0.0 – 10.0 m
0 m
92
BOOSTER
See parameter 101
If differential pressure is set
CIRCULATORS
See parameter 101